Rectifier Sizing Calculator (N+1)
How many rectifier modules does the site need?
Your numbers
Your results
Rectifier Sizing Calculator (N+1) by TheCalcTools
How the Rectifier Sizing Calculator (N+1) works
Enter the site DC load current and the battery bank size.
The rectifiers must supply the load plus the battery charge current; add a growth margin.
Divide by the module rating, round up for N, then add redundant modules.
The formula
Worked example
Using the default values shown in the calculator:
| DC load current (A) | 60 |
|---|---|
| Battery bank (Ah) | 400 |
| Battery charge current (C-rate, e.g. 0.1) | 0.1 |
| Rectifier module rating (A) | 50 |
| Growth margin (%) | 20 % |
| Redundant modules | 1 |
- Required current = 60 × 1.2 + 400 × 0.1 = 112.0 A.
- Modules: 3 for the load, 4 with redundancy, giving 200 A installed (10.8 kW).
Result:
| Required DC current (A) | 112.0 |
|---|---|
| Modules for the load (N) | 3 |
| Modules with redundancy | 4 |
| Installed capacity (A) | 200 |
| Installed power at 54 V (kW) | 10.8 |
Frequently asked questions
What does N+1 mean?
N modules supply the load and one extra module covers a single module failure without losing capacity.
Why 54 V for power?
A 48 V telecom system floats at about 53.5–54.5 V, so output power is current × float voltage.
Sources and further reading
Related calculators
More in Telecom Power & Passive Infrastructure · All calculators