Telecom Power & Passive Infrastructure

Battery Charge Time Calculator

How long until the batteries are back to full after an outage?

Your numbers

%
%

Your results

Ah to return
Ah to return
—
Charge time (hours)
—
Charge rate (C/n)
—
Charge current check
—

Battery Charge Time Calculator by TheCalcTools

How the Battery Charge Time Calculator works

Enter the bank capacity and how deeply it was discharged.

Enter the charge current the rectifier can spare after supplying the load.

Time = Ah to return ÷ (current × efficiency). The last 10–20% takes longer in practice due to the absorption stage.

The formula

Time = capacity × discharged fraction ÷ (charge current × efficiency)

Worked example

Using the default values shown in the calculator:

Bank capacity (Ah)400
Discharged (% of capacity)60 %
Charge current (A)40
Charge efficiency (%)90 %
  1. Ah to return = 400 × 60% = 240 Ah.
  2. At 40 A and 90% efficiency, charging takes about 6.7 hours (C/10.0).

Result:

Ah to return240
Charge time (hours)6.7
Charge rate (C/n)C/10.0
Charge current checkWithin common limits (0.05C–0.2C)

Frequently asked questions

What is a safe charge current?

VRLA batteries are commonly charged at 0.1–0.2C (10–20% of Ah). Check the manufacturer’s limit and the temperature compensation.

Why does charging take longer than calculated?

As voltage reaches the absorption level, the current tapers. Allow extra time, especially to reach 100%.

Sources and further reading

More in Telecom Power & Passive Infrastructure · All calculators

This calculator gives estimates for planning only. Electrical installations must be designed, checked and carried out by qualified personnel following local codes and the equipment manufacturer's data. Never rely on this result alone for safety-critical decisions. See our disclaimer.