3-Phase Cable Voltage Drop Calculator

Check whether the cable run is too long for the load.

Your numbers

Your results

Voltage drop (V)
Voltage drop (V)
—
Voltage drop (%)
—
Cable loss (W)
—
Check
—

3-Phase Cable Voltage Drop Calculator by TheCalcTools

How the 3-Phase Cable Voltage Drop Calculator works

Choose the conductor material, size, length and load current.

Resistance per metre is resistivity ÷ area; reactance is taken as about 0.08 mΩ/m.

Voltage drop = √3 × I × L × (R cosφ + X sinφ) for three-phase, 2 × I × L × (…) for single-phase.

The formula

ΔV (3-ph) = √3 × I × L × (R cos φ + X sin φ)R = ρ ÷ A

Worked example

Using the default values shown in the calculator:

ConductorCopper (~0.0225 Ω·mm²/m at 70°C)
Conductor size (mm²)35
One-way length (m)80
Load current (A)60
Power factor0.85
SupplyThree-phase 400 V
  1. R = 0.0225 ÷ 35 = 0.000643 Ω/m.
  2. ΔV = √3 × 60 × 80 × (R cos φ + X sin φ) = 4.89 V (1.22%). Cable loss ≈ 555 W.

Result:

Voltage drop (V)4.89
Voltage drop (%)1.22%
Cable loss (W)555
CheckWithin 5% (typical limit)

Frequently asked questions

What is an acceptable voltage drop?

Many standards limit total drop from source to load to around 5%, sometimes 3% for lighting. Check your local code.

Is this accurate?

It is an estimate. Use cable manufacturers’ tables for exact resistance and reactance, installation method, temperature and grouping factors.