Telecom Power & Passive Infrastructure

Transformer Current and Fault Level Calculator

Full-load amps and fault level for a distribution transformer.

Your numbers

%

Your results

Primary full-load current (A)
Primary full-load current (A)
—
Secondary full-load current (A)
—
Secondary fault current (kA)
—
Fault level (MVA)
—

Transformer Current and Fault Level Calculator by TheCalcTools

How the Transformer Current and Fault Level Calculator works

Enter the transformer’s kVA, primary and secondary voltages and impedance (%Z) from its nameplate.

Full-load current = kVA ÷ (√3 × V).

The secondary fault current assumes an infinite source: I_sc = I_full-load ÷ Z.

The formula

I = kVA × 1,000 ÷ (√3 × V)I_sc = I_FL ÷ (Z% ÷ 100)

Worked example

Using the default values shown in the calculator:

Transformer rating (kVA)400
Primary voltage (V)11000
Secondary voltage (V)400
Impedance voltage (%)4 %
  1. Primary: 400,000 ÷ (√3 × 11,000) = 21.0 A. Secondary: 577.4 A.
  2. Fault current at 4% = 14.43 kA (10.00 MVA).

Result:

Primary full-load current (A)21.0
Secondary full-load current (A)577.4
Secondary fault current (kA)14.43
Fault level (MVA)10.00

Frequently asked questions

Is the fault current this high in practice?

This is the maximum from the transformer with an infinite upstream source. Real values are lower once source impedance and cable impedance are included.

Why does it matter?

Breakers and busbars must be rated for at least the prospective fault current at their location.

Sources and further reading

More in Telecom Power & Passive Infrastructure · All calculators

This calculator gives estimates for planning only. Electrical installations must be designed, checked and carried out by qualified personnel following local codes and the equipment manufacturer's data. Never rely on this result alone for safety-critical decisions. See our disclaimer.