Circuit Breaker Size Calculator

Pick the next standard breaker size above your load.

Your numbers

%
125% is common practice for continuous loads; follow your local code.

Your results

Load current (A)
Load current (A)
—
Minimum rating with margin (A)
—
Standard breaker rating (A)
—
Headroom above load
—

Circuit Breaker Size Calculator by TheCalcTools

How the Circuit Breaker Size Calculator works

Enter the load, power factor, voltage and supply type.

The tool calculates the load current and applies the continuous-load margin.

It then picks the next standard rating from the common series.

The formula

I = P ÷ (√3 × V × PF) for three-phaseBreaker ≥ I × (1 + margin)

Worked example

Using the default values shown in the calculator:

Load (kW)20
Power factor0.85
Line voltage (V)400
SupplyThree-phase
Continuous-load margin (%)25 %
  1. Load current = 34.0 A.
  2. With a 25% margin the minimum is 42.5 A, so choose a 50 A breaker (47% headroom).

Result:

Load current (A)34.0
Minimum rating with margin (A)42.5
Standard breaker rating (A)50
Headroom above load47%

Frequently asked questions

Does the breaker also protect the cable?

Yes. The cable’s current rating must be at least the breaker rating (or the design current if using adjustable settings). Check the cable table and the voltage drop.

What about short-circuit rating?

The breaker’s breaking capacity must exceed the prospective fault current at its location. This calculator does not check that.

Sources and further reading

More in Telecom Power & Passive Infrastructure · All calculators

This calculator gives estimates for planning only. Electrical installations must be designed, checked and carried out by qualified personnel following local codes and the equipment manufacturer's data. Never rely on this result alone for safety-critical decisions. See our disclaimer.